Oliju SGR Sewage Grinder Submersible Pumps
The Oliju SGR sewage grinder submersible pumps are heavy cast iron grinder pumps for domestic and light commercial sewage that has to be lifted further or higher than a standard sewage pump can manage. A stainless steel cutter shreds soft solids and fibres, including toilet waste, before they reach the open impeller, so the macerated sewage can be pumped through a 1½” or 2″ rising main rather than a large-bore pipe.
Oliju builds the SGR with a cast iron pump body, impeller and motor casing, a stainless steel shaft and an oil-filled motor with class F insulation. The motor is protected by double seals, lip seals and a silicon carbide mechanical seal. The front outlet suits guide rail installation, and Oliju rates the pumps for immersion to 10 metres. Single-phase versions have a built-in capacitor and come with a protection box.
SGR 40 or SGR 50: choosing a size
The first number in the model code is the outlet size in millimetres and the second is the motor rating, so the SGR 50.220 has a 2″ (50 mm) outlet and a 2.2 kW motor. The SGR 40.150 has a 1½” outlet, reaches 21 metres of head and delivers up to about 275 litres per minute. The SGR 50.220 reaches 30 metres and about 380 litres per minute, and holds far more of its flow as the head rises: at 200 litres per minute it still gives around 22 metres, against around 8 metres for the SGR 40.
Supply and control. Both sizes come in 230v single-phase and 400v three-phase. The 230v pumps are available as manual models, which need a separate float switch or control panel, or as automatic models with a float switch fitted. The 400v pumps run under your own control panel.
For lighter single-phase duties, including 110v site supplies, see the JS GS grinder range. For heads beyond 30 metres, the Pentax DTR high head grinder range goes up to 54.6 metres.
| Model | Supply | Operation | Outlet | Max Flow (l/min) | Max Head (m) | Head at 200 l/min (m) | Motor (kW) |
|---|---|---|---|---|---|---|---|
| SGR 40.150 Manual 230v | 230v 1~ | Manual | 1½” | 275 | 21 | 8.1 | 1.5 |
| SGR 40.150 Automatic 230v | 230v 1~ | Automatic | 1½” | 275 | 21 | 8.1 | 1.5 |
| SGR 40 400v | 400v 3~ | Manual | 1½” | 275 | 21 | 8.1 | Ask us |
| SGR 50.220 Manual 230v | 230v 1~ | Manual | 2″ | 380 | 30 | 21.7 | 2.2 |
| SGR 50.220 Automatic 230v | 230v 1~ | Automatic | 2″ | 380 | 30 | 21.7 | 2.2 |
| SGR 50.220 400v | 400v 3~ | Manual | 2″ | 380 | 30 | 21.7 | 2.2 |
Figures are from Oliju’s 50 Hz data. Maximum head is at zero flow and maximum flow is at zero head. Oliju has listed the three-phase SGR 40 at both 1.2 kW and 1.5 kW over the years, so call us to confirm the motor fitted to current stock. Click through to any model for full specifications.
Showing all 6 results
275 l/min · 21 m · 230v
Single-phase 230v Oliju grinder pump with a 1.5 kW motor and a 1½" outlet. Up to 21 m head ...Read More£817.09 +VAT
275 l/min · 21 m · 230v
Automatic single-phase Oliju grinder pump with a float switch fitted, a 1.5 kW motor and a 1½" outlet. Up ...Read More£837.79 +VAT
380 l/min · 30 m · 230v
Single-phase 230v Oliju grinder pump with a 2.2 kW motor and a 2" outlet. Up to 30 m head ...Read More£1,115.17 +VAT
380 l/min · 30 m · 230v
Automatic single-phase Oliju grinder pump with a float switch fitted, a 2.2 kW motor and a 2" outlet. Up ...Read More£1,137.94 +VAT
275 l/min · 21 m · 400v
Three-phase 400v Oliju SGR 40 grinder pump with a 1½" outlet. Up to 21 m head and about 275 ...Read More£698.41 +VAT
380 l/min · 30 m · 400v
Three-phase 400v Oliju grinder pump with a 2.2 kW motor (4.6 A) and a 2" outlet. Up to 30 ...Read More£960.61 +VAT
Where to Use Oliju SGR Grinder Pumps
Oliju designs the SGR for water loaded with solids and fibres, including all the waste water from a house, toilets included. Typical jobs are a basement bathroom or utility room below the sewer, an annexe, holiday let or outbuilding with a long run back to the drain, and small commercial premises where gravity drainage is not possible. Because the cutter reduces the waste to a slurry, you can run a 1½” or 2″ rising main instead of trenching in a large-bore pipe.
Size the pump on total head, not just the vertical lift. Friction in a long, small-bore pipe adds metres quickly, and a grinder that looks right on maximum head can deliver very little flow at the duty point. Our guides to pump head and flow rate and discharge pipe sizing explain the sums, and how a sewage grinder pump works covers what the cutter does. If the drain is close and only a few metres up, a vortex sewage pump that passes solids whole may be the simpler choice.
Frequently Asked Questions
What do the numbers in the Oliju SGR model codes mean?
The first number is the outlet size in millimetres (40 for a 1½” outlet, 50 for a 2″ outlet) and the second is the motor rating, so 150 is 1.5 kW and 220 is 2.2 kW. Oliju adds .1M for a 230v manual pump, .1A for a 230v pump with a float switch and .3 for a 400v three-phase pump.
When should I choose the SGR 50.220 over the SGR 40.150?
Choose the SGR 50.220 when the head is high or you need a good flow at height. It reaches 30 metres against 21 metres for the SGR 40.150, and at 200 litres per minute it still gives around 22 metres, where the SGR 40 is down to about 8 metres. The SGR 40.150 is the lighter, smaller pump (26.5 kg against 36 kg) for moderate lifts.
Do the manual SGR pumps need a float switch?
Yes. A manual pump runs whenever it has power, so in a permanent sump it needs a float switch or a control panel to start and stop it. The automatic 230v models have a float switch fitted. The 400v pumps need a three-phase control panel with suitable motor protection.
Can the SGR be installed on a guide rail?
Yes. Oliju gives the SGR a front outlet for guide rail installations, so the pump can be lifted out of a chamber for servicing without disconnecting the pipework. We also stock an SGR 40 adapter to suit a BA50; call us to check the right fittings for your chamber.
How long is the power cable?
The SGR 40 comes with 10 metres of H07RN-F neoprene cable and the SGR 50 with 20 metres. Oliju lists other lengths on request, so ask us before ordering if your control panel is further away.
What should not go into an SGR grinder pump?
The cutter is designed for soft solids and fibres in sewage. Sand, gravel, stones and builders’ debris wear or jam it, so keep site run-off out of the sump. Oliju rates the pump for immersion to 10 metres; ask us before using it in a deeper chamber or on anything other than sewage and dirty water.
For help choosing an SGR model for your head, pipe run and supply, call the AES Rewinds team on 01252 515169 or email sales@aesrewinds.com. You can also browse all sewage pumps, or the three-phase JS GST grinder range.
Free, independent advice
Need help choosing? Ask our team
Not sure it is the right pump or motor for the job? Send us a question and our team will reply, or call us now. We have been supplying, repairing and rewinding pumps since 1948.
Monday to Friday, 8.30am to 5.30pm
Send us a question
We reply within one working day.